LV Power & Control Cable 1100V
PVC Copper & Aluminium Conductor Heavy Duty
Single & Multicore Copper & Aluminium Armoured & Unarmoured Indoors or Outdoors in cable ducts, cable trays, conduits or underground locations under mechanical stresses in power and switching stations. Local distribution systems, Industrial and Commercial units for basic power & lighting purpos.
POWER ABLES CONFORMING TO IS: 1554 (PART 1) AMENDED UPTO DATE |
||
S. No. | Cable Type | Sizes |
1 | 1.1 W Single Core, Aluminium/Copper Conductor, PVC Insulated Aluminium Wire / Strip
Armoured/Un-Armoured & PVC Sheathed Cables |
1.5sq mm to
1000 sq mm |
2 | 1.1 kV Twin Core, Aluminium Conductor, PVC Insulated, Inner Sheathed, Armoured/
Unarmoured PVC Sheathed Cables |
1.5sq mm to 500sq mm |
3 | 1.1 kV Three Core, Aluminium/Copper Conductor, PVC Insulated, Inner Sheathed,
Armored/ Unarmoured PVC Sheathed Cables |
1.5sq mm to 500sq mm |
4 | 1.1 kV 3.5 Core, Aluminium/Copper Conductor, PVC Insulated, Inner Sheathed,
Armored/Unarmoured PVC Sheathed Cables |
25sq mm to
500sq mm |
5 | 1.1 W Four Core, Aluminium/Copper Conductor, PVC Insulated, Inner Sheathed,
Armored/Unarmoured PVC Sheathed Cables |
1.5sq mm to 400sq mm |
CONTROL CABLE CONFIRMING TO IS: 1554 (PART 1) AMENDED UPTO DATE | ||
6 | 1.1 kV, Annealed High Conductivity Solid Copper Conductor, 1.5 & 2.5Sq.mm
PVC Insulated, Inner Sheathed, Armoured / Unarmoured PVC Sheathed Control Cables |
2Core to 61
Core |
CURRENT RATING OF COPPER ARMOURED / UNOURMOUD CABLES (650 / 1100 V GRADE IN AIR.) | |||||
Area | Twin Core | 3, 3.5 & 4 Core | Area | Twin Core | 3, 3.5 & 4 Core |
Sqm | Amp. | Amp | Sqm | Amp. | Amp |
1.5 | 20 | 17 | 70 | 195 | 165 |
2.5 | 27 | 24 | 95 | 230 | 200 |
4.0 | 35 | 30 | 120 | 265 | 235 |
6.0 | 45 | 39 | 150 | 305 | 265 |
10.0 | 60 | 52 | 185 | 350 | 305 |
16.0 | 78 | 66 | 240 | 410 | 355 |
25.0 | 105 | 90 | 300 | 465 | 400 |
35.0 | 125 | 110 | 400 | 530 | 455 |
50.0 | 155 | 135 | - | - | - |